Specifications Guide for Thor Duct® 2.0
We have a suggested wording for specifiers to use for Thor Duct® 2.0 applications.
Smoke Extraction Ductwork
For Smoke Extraction ductwork, to ensure your specification is clear and includes all relevant codes we suggest your specification can be written as follows:
Single Compartment
All Thor Duct® 2.0 Smoke Extract ductwork to standard EN12101-7 and tested to EN1366-9 for single compartment.
- Classified EN13501-4
- Test standard EN1366-9
- Maximum size 1900x1700mm
- 30mm Flange duct connections
- Insulation not required
- Integrity (E) rating derived from the compartment rating
- 600°C smoke conditions as per EN1366-9 fire test
- CE marked or UKCA as appropriate
- Where required, drains type ST-K as tested may be fitted
- Grilles for the smoke duct type Lindab RGS as tested
- Where single compartment ducts are connected to multi compartment ducts through a fire compartment wall, penetration by a self supporting Thor Duct Tunnel penetration detail
- Performance E600 (ho)S 1500Pa Single
Multi Compartment
All Thor Duct® 2.0 Smoke Extract ductwork to standard EN12101-7 and tested to EN1366-8 for multi compartment.
- Classified EN13501-4
- Test standard EN1366-1 and EN1366-8
- Maximum size 1250x1000mm. Larger sizes to be provided as split ducts
- 25mm thickness pre-Insulated ductwork sections delivered from an FPC production facility
- CE marked or UKCA as appropriate in compliance with Regulation EU305:2011
- Integrity and insulation (EI) performance derived from the compartment requirement, giving regard to all the dependent compartments being crossed by the duct work
- 30mm Flange duct connections
- Access door (maximum 450x450mm) tested to EN1366-8
- Flange collars not to exceed 25mm in thickness for co-ordination, fitted on site
- Where required, drains type ST-K as tested may be fitted
- Grilles for the smoke duct type Lindab RGS as tested
- Penetration self-supporting to wall structure by way of Thor Duct® 2.0 Tunnel
- Performance EI90 (ho, ve)S 500Pa Multi
Fire Rated Ductwork
For Fire Rated ductwork, the suggested specification can be written as follows.
All Thor Duct® 2.0 fire rated and pressurisation ductwork will be to standard prEN15871 and tested to EN1366‑1 vertically and horizontally for type A (fire outside) and type B (fire inside).
- Classified EN13501-3
- Test standard EN1366-1
- Maximum size 1250x1000mm
- 30mm Flange duct connections
- Access door (maximum 450x450mm) tested to EN1366-1
- For (EI) requirements, delivered pre-insulated with 25mm thick Insulation
- Flange collars not to exceed 25mm in thickness for co-ordination, fitted on site
- For (E) Integrity only requirements, delivered uninsulated
- Integrity and insulation (EI) performance derived from the compartment requirement, giving regard to all the dependent compartments being crossed by the duct work
- Penetration self-supporting to wall structure by way of Thor Duct® 2.0 Tunnel
- Where the fire duct crosses a protected route, the EI requirement of the protected route must be maintained as required in BS9999:2017
- Where required, drains type ST-K as tested may be fitted
- Grilles for the fire duct type Lindab RGS as tested
- For ductwork sizes above 1250x100mm and below 2500x1250mm refer to the original Thor Duct system with onsite wrapping
- Kitchen extract ductwork to be EN1366-1 duct from the back of the canopy all the way to atmosphere
- Thor Duct® that is insulated and exposed to the elements must be protected from moisture accordingly
- Performance EI90 (Ho, Ve i<>o)
EI120 (Ho, Ve i<o)
43’ kitchen extract combustible linings
82' kitchen extract combustible linings with super collars
We have a suggested wording for specifiers to use for Thor Duct® 2.0 applications.
Where Thor Duct® 2.0 doesn't meet your technical requirements please select an
original Thor Duct® product to suit your specification and identified risk:
Blank
Standard
Classification
Applications
Tightness
Thor Duct®
Smoke Extract
EN12101-7
EN13501-4
✓ Single and multi-compartment
✓ Vertical and horizontal, at 1500
pa
✓ Smoke extract
Class S
Thor Duct®
Kitchen Extract
pr EN15871
EN13501-3
✓ Vertical and horizontal
✓ Kitchen extract
Class S
Thor Duct®
Fire Ductwork
pr EN15871
EN13501-3
✓ Vertical and horizontal
✓ Passive and pressurisation
Class S